Basit öğe kaydını göster

dc.contributor.authorAğırman, Aleyna
dc.contributor.authorÇetin, Yunus Emre
dc.contributor.authorAvcı, Mete
dc.contributor.authorAydın, Orhan
dc.date.accessioned2020-12-19T19:34:34Z
dc.date.available2020-12-19T19:34:34Z
dc.date.issued2020
dc.identifier.citationAğırman, A., Çetin, Y.E., Avcı, M. & Aydın, O. (2020). Effect of air exhaust location on surgical site particle distribution in an operating room. Building Simulation, 13(5), 979-988. https://doi.org/10.1007/s12273-020-0642-1en_US
dc.identifier.issn1996-3599
dc.identifier.issn1996-8744
dc.identifier.urihttps://doi.org/10.1007/s12273-020-0642-1
dc.identifier.urihttps://hdl.handle.net/11436/1125
dc.descriptionCETIN, Yunus Emre/0000-0003-0165-2900;en_US
dc.descriptionWOS: 000536446000001en_US
dc.description.abstractThis study investigates effect of exhaust outlet location on airflow and particle distribution in an operating room with laminar ventilation system (LAF) via computational fluid dynamics (CFD). Four different exhaust opening configurations are comparatively examined: floor level, central level, ceiling level and floor & ceiling level. Three different particle diameters (5,10 and 20 mu m) are considered for a constant value of the air change rate (30 ACH). Deposited particle numbers to operating table and to instrument table are given and compared for different particle diameters and exhaust outlet cases. It is shown that the exhaust configuration in which both floor & ceiling level air outlets employed together shows the best performance in terms of lowest particle deposition to the operating table. For this case, compared to original floor level exhaust outlet design, the total number of particles deposited on the operating table decreased by 64% for the smallest particle diameter (5 mu m) and 26% for the largest particle diameter (20 mu m).en_US
dc.language.isoengen_US
dc.publisherTsinghua Univ Pressen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectOperating roomen_US
dc.subjectExhaust outleten_US
dc.subjectParticle depositionen_US
dc.subjectCFDen_US
dc.titleEffect of air exhaust location on surgical site particle distribution in an operating roomen_US
dc.typearticleen_US
dc.contributor.departmentRTEÜ, Mühendislik ve Mimarlık Fakültesi, Makine Mühendisliği Bölümüen_US
dc.contributor.institutionauthorAvcı, Mete
dc.identifier.doi10.1007/s12273-020-0642-1
dc.identifier.volume13en_US
dc.identifier.issue5en_US
dc.identifier.startpage979en_US
dc.identifier.endpage988en_US
dc.relation.journalBuilding Simulationen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US


Bu öğenin dosyaları:

Thumbnail

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster