Basit öğe kaydını göster

dc.contributor.authorAkbulut, Uğur
dc.contributor.authorKıncay, Olcay
dc.contributor.authorUtlu, Zafer
dc.date.accessioned2020-12-19T19:56:18Z
dc.date.available2020-12-19T19:56:18Z
dc.date.issued2016
dc.identifier.citationAkbulut, U., Kincay, O., Utlu, Z. (2016). Analysis of a wall cooling system using a heat pump. Renewable Energy, 85, 540-553. https://doi.org/10.1016/j.renene.2015.07.005en_US
dc.identifier.issn0960-1481
dc.identifier.urihttps://doi.org/10.1016/j.renene.2015.07.005
dc.identifier.urihttps://hdl.handle.net/11436/2711
dc.descriptionakbulut, ugur/0000-0002-9317-3298en_US
dc.descriptionWOS: 000363344800052en_US
dc.description.abstractIn this study, a vertical ground source heat pump wall cooling system that belongs to the Yildiz Renewable Energy House at the Davutpasa Campus of Yildiz Technical University was studied both experimentally and theoretically. the principal objective was to perform a system analysis to determine the parameters that allow the energy usage of the cooling system to be as low as possible. For this reason, a system working in a low temperature regime was chosen. the examination includes energy and exergy analyses conducted during the period between 1 July and 30 September 2012, which is described as the "Summer Session". By using the data that were collected on a per-second basis during these processes and conveyed to a MySQL database, "The moments when the heat pump is activated" were detected, and the "Monthly Average Values" were analyzed. Thus, a theoretical analysis was conducted for the Cooling Session and its correlations. These correlations were used in the energy and exergy analyses. According to the analysis results, the energy and exergy efficiencies of the entire system were found to be 74.85% and 29.90%, respectively, and the Wall Heating Cooling System panels calculated the heat with energy and exergy efficiencies of 90.29% and 80.4%, respectively. (C) 2015 Elsevier Ltd. All rights reserved.en_US
dc.language.isoengen_US
dc.publisherPergamon-Elsevier Science Ltden_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectCoolingen_US
dc.subjectEnergyen_US
dc.subjectExergyen_US
dc.subjectHeat pumpen_US
dc.subjectRenewable energyen_US
dc.subjectWall coolingen_US
dc.titleAnalysis of a wall cooling system using a heat pumpen_US
dc.typearticleen_US
dc.contributor.departmentRTEÜ, Mühendislik ve Mimarlık Fakültesi, Makine Mühendisliği Bölümüen_US
dc.contributor.institutionauthorAkbulut, Uğur
dc.identifier.doi10.1016/j.renene.2015.07.005
dc.identifier.volume85en_US
dc.identifier.startpage540en_US
dc.identifier.endpage553en_US
dc.relation.journalRenewable Energyen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US