dc.date.issued2016
dc.identifier.citationAkbulut, U., Utlu, Z., kincay, O. (2016). Exergy, exergoenvironmental and exergoeconomic evaluation of a heat pump-integrated wall heating system. Energy, 107, 502-522. https://doi.org/10.1016/j.energy.2016.04.050en_US
dc.identifier.issn0360-5442
dc.identifier.issn1873-6785
dc.identifier.urihttps://doi.org/10.1016/j.energy.2016.04.050
dc.identifier.urihttps://hdl.handle.net/11436/2450
dc.descriptionakbulut, ugur/0000-0002-9317-3298en_US
dc.descriptionWOS: 000378660500042en_US
dc.description.abstractIn this study, a vertical ground source heat pump wall heating system belonging to the Yildiz Renewable Energy House on the Davutpasa Campus of Yildiz Technical University was experimentally and theoretically studied. the examination included energy, exergy, exergoenvironmental and exergoeconomic analyses from 1 January 2013 to 30 March 2013 (i.e., the "Winter Session"). Data were collected and uploaded to a MySQL database. "The moments when the heat pump is activated" was detected and "Monthly Average Values" were analysed. Theoretical analyses were conducted for the Winter Session and correlated with the experimental results. This study includes exergetically, exergoeconomically, and exergoenvironmental evaluate a building and its heating system from the generation stage to the envelope of the building. the findings are based on applying a low exergy, exergoenvironmental and exergoeconomic analysis to investigate the system" performance. the energy and exergy efficiencies of the entire system were 67.36% and 27.40%, respectively, and the energy and exergy efficiencies of the wall heating system panels were 86.61% and 82.90%, respectively. the monthly average exergy-based environmental impact value was 0.212 mPts/s. the exergoeconomic factors changed from 74.97% to 75.77%. (C) 2016 Elsevier Ltd. All rights reserved.en_US
dc.language.isoengen_US
dc.publisherPergamon-Elsevier Science Ltden_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectEnergyen_US
dc.subjectExergyen_US
dc.subjectHeat pumpen_US
dc.subjectExergoenvironmentalen_US
dc.subjectExergoeconomicen_US
dc.subjectWall heatingen_US
dc.titleExergy, exergoenvironmental and exergoeconomic evaluation of a heat pump-integrated wall heating systemen_US
dc.typearticleen_US
dc.contributor.departmentRTEÜ, Mühendislik ve Mimarlık Fakültesi, Makine Mühendisliği Bölümüen_US
dc.contributor.institutionauthorAkbulut, Uğur
dc.identifier.doi10.1016/j.energy.2016.04.050
dc.identifier.volume107en_US
dc.identifier.startpage502en_US
dc.identifier.endpage522en_US
dc.relation.journalEnergyen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US


Bu öğenin dosyaları:

Thumbnail

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster