Basit öğe kaydını göster

dc.contributor.authorAğırman, Aleyna
dc.contributor.authorÇetin, Yunus Emre
dc.contributor.authorAvcı, Mete
dc.contributor.authorAydın, Orhan
dc.date.accessioned2020-12-19T19:32:24Z
dc.date.available2020-12-19T19:32:24Z
dc.date.issued2020
dc.identifier.citationAğırman, A., Çetin, Y.E., Avcı, M. & Aydın, O. (2020). Effect of laminar airflow unit diffuser size on pathogen particle distribution in an operating room. Science and Technology For the Built Environment, 27(4), 402-413. https://doi.org/10.1080/23744731.2020.1816405en_US
dc.identifier.issn2374-4731
dc.identifier.issn2374-474X
dc.identifier.urihttps://doi.org/10.1080/23744731.2020.1816405
dc.identifier.urihttps://hdl.handle.net/11436/1011
dc.descriptionCETIN, Yunus/0000-0003-0165-2900en_US
dc.descriptionWOS: 000568950700001en_US
dc.description.abstractOperating room ventilation is quite important to protect patients from infection risk inside a surgical field. the laminar flow units (LAF) used in these applications contribute to removal of pathogen particles from the operation area by creating a protection zone on the surgical field. in this study, effect of LAF diffuse size on airflow and particle distribution in an operating room is investigated using computational fluid dynamics (CFD). Three different diffuser sizes (1.8 m x 2.4 m, 2.4 m x 2.4 m, 3.2 m x 3.2 m) and three different particle diameters (5 mu m, 10 mu m, 20 mu m) are examined. in the modeling of airflow and particle motion, the Realizable k-epsilon turbulence model and Lagrangian approach are used, respectively. the distributions of airflow and particles originated from the surgical team are analysed. Also, the air change efficiency is predicted as for the entire operating room and for the breathing zone. the results reveal that the LAF diffuser size has a decisive role in air velocity and contaminant distribution in the operating room. It is seen that the amount of particles deposited on the operating table could be reduced up to 73% by increasing the diffuser size.en_US
dc.language.isoengen_US
dc.publisherTaylor & Francis Incen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectBacterial contaminationen_US
dc.titleEffect of laminar airflow unit diffuser size on pathogen particle distribution in an operating roomen_US
dc.typearticleen_US
dc.contributor.departmentRTEÜ, Mühendislik ve Mimarlık Fakültesi, Makine Mühendisliği Bölümüen_US
dc.contributor.institutionauthorAvcı, Mete
dc.identifier.doi10.1080/23744731.2020.1816405
dc.relation.journalScience and Technology For the Built Environmenten_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US


Bu öğenin dosyaları:

Thumbnail

Bu öğe aşağıdaki koleksiyon(lar)da görünmektedir.

Basit öğe kaydını göster